DatasheetQ Logo
Electronic component search and free download site. Transistors,MosFET ,Diode,Integrated circuits

EN61000-4-6 Просмотр технического описания (PDF) - General Semiconductor

Номер в каталоге
Компоненты Описание
производитель
EN61000-4-6
GE
General Semiconductor GE
EN61000-4-6 Datasheet PDF : 7 Pages
1 2 3 4 5 6 7
GE Energy
CAR2512FP series rectifier
Input: 90Vac to 264Vac; Output: 12 Vdc @ 208A; 3.3Vdc or 5 Vdc @ 1A
12Vdc MAIN OUTPUT (continued)
Parameter
Remote ON/OFF delay time
Turn-ON rise time (10 – 90% of Vout)
Transient response 50% step [10%-60%, 50% - 100%]
(dI/dt – 1A/outµs, recovery 300µs)
Programmable range (hardware & software)
Overvoltage protection, latched
(recovery by cycling OFF/ON via hardware or software)
Output current [V
Current limit, Hiccup (programmable level)
Active current share
Vin = HL
Vin = LL
HL / LL
Device
All
All
All
All
All
All
All
All
Symbol
Vout
Iout
Min
-5
10.8
13.8
0
110/110
-5
Typ
Max
Unit
40
ms
50
ms
+5
%Vout
13.2
Vdc
14.8
15.8
Vdc
208
100
130/140
+5
Adc
% of FL
% of FL
AUXILIARY OUTPUT
Parameter
Set point
Overall regulation (load, temperature, aging)
Ripple and noise
Output current
Overload protection -
Overvoltage protection
Isolation Output/Frame
Device Symbol
Min
All
Vout
All
Vout
-5
All
All
Iout
0
Typ
Max
3.3 / 5.0
+5
50
1
Unit
Vdc
%
mVp-p
Adc
All
100
Vdc
Environmental, Reliability
Parameter
Min
Typ
Max
Units
Notes
Ambient Temperature
Operating -104
Altitude Operating
Power Derating
50
1524/5k
2.5
2.0
°C
m / ft
%/°C
C/1000 ft
Air inlet from sea level to 5,000 feet.
51°C to 70C
Above 5,000 ft
Storage -40
Altitude non-operating
85
8200/30k
°C
m / ft
Acoustic noise
55
dbA
Full load
Over Temperature Protection
125/110
°C
Shutdown / restart
Humidity
Operating
30
Storage
10
95
95
%
Relative humidity, non-condensing
Shock and Vibration acceleration
6
Grms
NEBS GR-63-CORE, Level 3, 20 -2000Hz, min 30 minutes
Earthquake Rating
4
Zone
NEBS GR-63-CORE, all floors, Seismic Zone 4 Designed
and tested to meet NEBS specifications.
Reliability
250,000
Hrs
Full load, 25C ; MTBF per SR232 Reliability protection
for electronic equipment, method I, case III,
Service Life
10
Yrs
Full load, excluding fans
4 Designed to start at an ambient down to -40°C; meet spec after 30 min warm up period, may not meet operational limits below -10°C.
July 18, 2012