DatasheetQ Logo
Electronic component search and free download site. Transistors,MosFET ,Diode,Integrated circuits

E5C4 Просмотр технического описания (PDF) - OMRON Corporation

Номер в каталоге
Компоненты Описание
производитель
E5C4
Omron
OMRON Corporation Omron
E5C4 Datasheet PDF : 8 Pages
1 2 3 4 5 6 7 8
E5C4
E5C4
Specifications
Ratings
Supply voltage
Operating voltage range
Power consumption
Input
Control mode
Setting method
Indication method
Control output
100/110, 200/220, 110/120, 220/240 VAC, 50/60 Hz
90% to 110% of rated supply voltage
Approx. 2 VA
Thermocouple (with sensor burnout detection circuit) or platinum resistance thermometer
ON/OFF or P control
Digital setting
Digital indication
Relay output:
SPDT, 3 A at 250 VAC, resistive load (switching capacity: 330 VA)
Voltage output for SSR: 10 mA at 5 VDC (with short-circuit protection)
H: 5±1 V; L: 0.5 V max.
Characteristics
Setting accuracy
±2% FS max.
Indication accuracy
±2% FS max.
Indication range
Within set temperature range
Hysteresis
Approx. 0.2% FS (fixed)
Proportional band
3% FS (fixed)
Proportional period
Relay output: Approx. 20 s
Voltage output: Approx. 2 s
Reset range (see note 1)
±1.5% FS min. (variable)
Insulation resistance
20 Mmin. (at 500 VDC)
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min between charged terminals and uncharged metallic parts
Vibration resistance
Shock resistance
Malfunction: 10 to 55 Hz, 0.3-mm double amplitude for 10 min each in X, Y, and Z directions
Destruction: 16.7 Hz, 4-mm double amplitude for 2 hrs each in X, Y, and Z directions
Malfunction: 147 m/s2 (15G), 3 times each in 6 directions
Destruction: 294 m/s2 (30G), 3 times each in 6 directions
Life expectancy
Mechanical: 10,000,000 operations min.
Electrical: 100,000 operations min. (3 A at 110 VAC, resistive load)
Ambient temperature
Operating: –10°C to 55°C (with no icing)
Ambient humidity
Operating: 45% to 85%
Enclosure ratings
Front panel: IEC standard IP40 (see note 2)
Terminals: IEC standard IP00
Weight
Approx. 200 g (with flush-mounting adapter)
Note: 1. The reset adjuster of any E5C4 model with ON/OFF control is used to correct any error of the set temperature that is displayed so
that the displayed temperature will coincide with the temperature that has been preset. The reset shaft of any E5C4 is used to reset
the E5C4 model with proportional control.
2. The model number of the special watertight cover conforming to IP66, NEMA4 is Y92A-48N.
2