Cassette Style
100 Watt AC-DC Converters
S Series PFC
Display Status of LEDs
Uo1 > 0.95...0.98Uo1 adj
06002
OK
i
Io L
Ui uv Ui min
Ui
Ui max Ui ov Ui abs
Uo1 > 0.95...0.98Uo1 adj Uo1 < 0.95...0.98Uo1 adj
OK
Io L
Io
Io nom
IoL
i
i
-50 V
LED off
TC max
Uinh threshold
TC
TPTC threshold
+0.8 V +2.4 V
LED Status undefined
Ui inh
+50 V
LED on
Fig. 22
LEDs "OK", "i" and "Io L"status versus input voltage
Conditions: Io £ Io nom, TC £ TC max, Uinh £ 0.8 V
Ui uv = undervoltage lock-out, Ui ov = overvoltage lock-out
LEDs "OK" and "Io L"status versus output current
Conditions: Ui min...Ui max, TC £ TC max, Uinh £ 0.8 V
LED "i"versus case temperature
Conditions: Ui min...Ui max, Io £ Io nom, Uinh £ 0.8 V
LED "i"versus Uinh
Conditions: Ui min...Ui max, Io £ Io nom, TC £ TC max
Battery Charging/Temperature Sensor
The LS are intended for lead acid battery charger applica-
tions. For an optimum battery charging and life expectancy
of the battery an external temperature sensor may be con-
nected to the R-input. The sensor is mounted as close as
possible to the battery pole and adjusts the output voltage
of the LS unit according to the temperature of the battery
(which is related to the load of the battery and the ambient
temperature).
Depending on the cell voltage and the temperature coeffi-
cient of the battery, different sensor types are available.
For more information please ask Power-One.
Cell voltage [V]
2.40
2.35
06123
Uo max
Test Sockets (Main output only )
Test sockets for measuring the output voltage Uo1 are lo-
cated at the front of the module. The positive test socket is
protected by a series resistor (see: Functional Description,
block diagrams). The voltage measured at the test sockets
is approximately 30 mV lower than the value measured at
the output terminals.
In case of double output units externally connected in se-
ries for Uo = 24 V, 30 V or 48 V the monitored output volt-
age is 12 V, 15 V or 24 V respectively.
2.30
Uz = 2.27 V, 3.5 mV/K
2.25
2.20
2.15 Uo nom
Uz = 2.23 V, 3.5 mV/K
2.10
0
[°C]
5 10 15 20 25 30 35 40 45 50
Fig. 17
Dependance of output voltage vs. temperature for defined
temperature coefficient.